Sydney Emergency Lighting are experts when it comes to emergency lighting system maintenance and compliance.
We can set up a schedule that will keep your system operational, protecting your business and fulfilling the legal requirements.
SCOPE OF WORK
Standard AS/NZS 2293.2 states, “that the emergency lighting installation be tested at six-monthly intervals by a discharge test to see that the fittings operate for the required duration of not less than 90 minutes.
In addition, at twelve-monthly intervals the fitting diffusers and reflecting surfaces are required to be cleaned.”
SEL follows these standards whilst carrying out maintenance and checking.
The process used is as follows-
• Prior to testing, our technicians visually inspect all fluorescent lights for darkened signs of aging or damage and replace where necessary.
• We then simulate a power failure by performing a discharge test for a period of 90 minutes. After this test the lights are then reinstated to their normal operating condition.
• All lights discharge test results, lamp replacements, repairs to be carried out and correct operation of the system will be recorded and a copy kept on site.
• A quotation for repair or replacement for any lights that fail the discharge test will be supplied.
• Responsible disposal of redundant batteries and components for recycling.
• Supply of 12 month certification on completion of testing and repairs.